High Energy Products
RPC's 3 Phase UPS systems and Hienergy series power protection systems offer total power continuity built with excellent power quality features and confirm to the latest Industry specifiactions. Our products are carefully designed with user centric features to mitigate the adverse effect that arises due to power quality problem on the critical equipments.
A wide range of UPS systems and power conditioning solutions are offered to cater to application based requirements. The latest generation of Clean Power technology products aims at being environmentally friendly, lower power consumption, precise power quality output, high efficiency and very high reliability. The products are time tested, proven and conform to International quality standards.
Applications
- Telecom / Internet Exchanges
- IT / ITES / BPO
- Data Centres
- Process Automation
- Manufacturing
- Health Care
Technical View |
|
Capacity |
1KVA-10KVA |
10KVA-40KVA |
10KVA-100KVA |
|
CHARGER |
|
Primary |
230V+15%-25% |
400V+-20% |
400V+-20% |
Voltage |
1Ø 3wire |
3Ø 4wire |
3Ø 4wire |
Frequency |
50Hz+/-5Hz |
50Hz+/-5Hz |
50Hz+/-5Hz |
Rectifier |
Full Controlled automatic float cum boost charger |
Power Factor |
>0.95 with Harmonic Suppression |
DC Voltage |
36-180 V |
240/360 V |
360/384 V |
|
|
INVERTER |
|
O/P Voltage |
230V+/-1%1Ø |
230V+/-1%1Ø |
400V+/-1%3Ø |
Waveform |
|
Pure sine |
|
Efficiency |
|
>93% |
|
Distortions |
THD less then 3% for 100% linear loads |
Control |
DSP/ Micro Processor based/Digital |
Power Device |
IGBT (Insulated Gate Bipolar Transistor) MOSFET |
O/P Frequency |
5Hz+/-0.5% |
Output Power Factor |
0.8 Lag to unity |
Overload Capacity Inverter 105% continues 125% for 10 Min150% for 1 Min |
|
|
GENERAL |
Topology |
Online double conversion |
Crest Factor |
Better than 3:1 |
Noise Level |
Less then 55 dba |
Indications |
Mains On, Inverter On, Out Put Normal, Mains Fail, Battery Low, Overload, Over Voltage, UPS Trip |
Alarms |
Audible alarm for low battery/mains failure |
Metering |
Input Voltage, Output Voltage, DC Voltage, Output Frequency (other Functions Optional) |
Protection |
Advanced electronic protection for device safety backed up with with MCBs and fast acting fuses. High Speed pulse balancing electronic high current trip with reset |
Temperature |
0-45°C |
Cooling |
Forced Air |
Cabinet |
Powder coated MS Box with wheels |
Back up Time |
As per Customer Requirement |
|